CABO
|
MHCSS
|
|
Light
and Ventilation
|
| Does
not allow kitchens to have artificial light in place of windows.
Requires half of required glazing
to be operable, except when a mechanical ventilation system
capable of supplying 15 CFM is provided.
Mechanical ventilation may be
omitted in bathrooms with 1.5 sf of operable glazing
Does not require kitchen
ventilation to vent to the outdoors. Allows unvented range
hoods.
|
Allows
kitchens to have artificial light in place of windows.
Requires half of required
glazing to be operable regardless of mechanical ventilation
requirement.
Requires all full bathrooms
and separate toilet compartments to have mechanical ventilation.
Requires kitchen
ventilation capable of providing 100 CFM to the outdoors.
Exhaust fan must be located within 10' of range or cook top.
|
|
CABO
|
MHCSS
|
|
Room
Sizes and Ceiling Heights
|
Room
sizes and heights:
- Habitable rooms not less
that 70 sf.
- Minimum dimension in
habitable rooms not less than 7'.
- In habitable rooms,
ceiling height not less that 7'-6" over 50% of room area.
Remaining area 5', minimum. Beams, girders, and
ducts may not project more than 6".
back to top
|
Room sizes and heights:
|
|
CABO
|
MHCSS |
|
Glazing
|
| Requires
safety glass on glazed panels within 24" of the arc of a door
in the closed position.
Requires safety glass in any panel greater than 9 sf.,
whose bottom edge is less than 18" from the floor, and is
within 36" of a walking surface.
Exempts a mirror mounted or hung on a door.
Does not require shutters or other protective coverings for
windows or doors in high wind zones.
|
Requires
safety glass on glazed panels within 12" of a door.
MHCSS does not address.
Requires safety glass in
unbacked mirrored wardrobe doors.
Requires walls, window and door
surroundings to be designed for placement of shutters or other
protective coverings in high wind zones.
|
| CABO |
MHCSS |
|
Exits,
Doorways and Egress
|
| Requires
no less than one conforming exit, with no requirements on the
location of the exit. x x
Conforming exit doors no less than 3' wide and
6'-8" tall. Hallways no less than 3' wide.
CABO does not address.
x x xxx
x xxx x
x x x x x x
On windows designed for emergency
egress, sill height no more than 44" high. CABO does
not limit height of operating hardware, or require operating
instructions posted on the window.
back to top
|
Requires
no less than two exterior exits, and limits the distance from any
bedroom to the nearest exit to 35'.
Conforming exit doors no less than 2'-4" wide
and 6'-2" tall. Hallways no less than 2'-4" wide.
Egress doors not to be located in a room with a
lockable interior door. Includes several other provisions
relating to required hardware for interior and exterior doors.
On windows designed for emergency egress, sill height must
be no more than 36" high, with operating hardware not more
than 54" high. Operating instructions must be
permanently posted on the window. Each bedroom must have an
egress window or an exterior door.
|
| CABO |
MHCSS |
|
Smoke
Detectors
|
| Requires
1 smoke detector in each bedroom.
Requires smoke detectors to be interconnected, and to have
a battery backup.
|
Requires
1 smoke detector in each bedroom area.
MHCSS does not
address.
|
| CABO |
MHCSS |
| Fire
Resistance |
| Limits
the use of foam plastic sheathing to 1/2 " thick, and
requires no less than 2" mineral wool insulation and 1/2"
gypsum wallboard covering.
Limits the use of foam plastic interior trim.
Limits smoke density of interior finishes to 450.
Limits flame spread classifications of walls and
ceilings to 200. Does not address other
configurations.
CABO does not address.
Requires flame spread rating of 75 or less and
smoke-developed rating of 450 or less for foam plastic thermal
insulating materials. Requires additional spread ratings
and smoke density factors for types of insulation materials other
than foam plastic.
back to top
|
Limits
the use of foam plastic sheathing to 3/8" thick, and
requires no less than 2" mineral wool insulation and
5/16" gypsum wallboard covering.
Does not limit the use of foam plastic interior trim.
Does not address smoke density of interior trim.
Limits flame spread classifications of walls to 200
and ceilings to 75. Provides additional flame spread
ratings for specific components of kitchen and bathrooms.
Requires "limited combustible materials" adjacent
to cooking ranges (maximum flame spread rating of 50), and doors
and enclosures around furnaces and water heaters (maximum flame
spread rating of 25).
Requires flame spread rating of 75 or less and
smoke-developed rating of 450 or less for foam plastic thermal
insulating materials.
|